Steppan, Rafael ; Simaku, Andi ; Kharrat, Achraf ; Hanson, Jutta (2024)
Influence of the Degree of Meshing on the Observability and Reliability of Monitoring Systems for Power System State Estimation.
In: IET Conference Proceedings, 2024 (5)
doi: 10.1049/icp.2024.203
Artikel, Bibliographie
Kurzbeschreibung (Abstract)
Power system state estimation approximates the state of the power system using a sparse metering infrastructure. For the optimal placement of measurement stations, observability and reliability requirements must be considered. In this work an optimal meter placement algorithm is used with an objective function that combines both monetary cost reduction and topological distribution, as well as the number of critical measurements and sets. In the investigation, the degree of meshing is increased or decreased by the closing of breakers and the switching off of lines, respectively. Simulation results of the CIGRE medium voltage network and the IEEE 30-bus network show that the minimum number of measurements for an observable system is not influenced by the degree of meshing. However, a higher degree of meshing has a positive effect on the reliability of the monitoring system as the number of critical measurements and sets is reduced.
Typ des Eintrags: | Artikel |
---|---|
Erschienen: | 2024 |
Autor(en): | Steppan, Rafael ; Simaku, Andi ; Kharrat, Achraf ; Hanson, Jutta |
Art des Eintrags: | Bibliographie |
Titel: | Influence of the Degree of Meshing on the Observability and Reliability of Monitoring Systems for Power System State Estimation |
Sprache: | Englisch |
Publikationsjahr: | 1 Juli 2024 |
Verlag: | IET |
Titel der Zeitschrift, Zeitung oder Schriftenreihe: | IET Conference Proceedings |
Jahrgang/Volume einer Zeitschrift: | 2024 |
(Heft-)Nummer: | 5 |
DOI: | 10.1049/icp.2024.203 |
URL / URN: | https://digital-library.theiet.org/doi/10.1049/icp.2024.2031 |
Zugehörige Links: | |
Kurzbeschreibung (Abstract): | Power system state estimation approximates the state of the power system using a sparse metering infrastructure. For the optimal placement of measurement stations, observability and reliability requirements must be considered. In this work an optimal meter placement algorithm is used with an objective function that combines both monetary cost reduction and topological distribution, as well as the number of critical measurements and sets. In the investigation, the degree of meshing is increased or decreased by the closing of breakers and the switching off of lines, respectively. Simulation results of the CIGRE medium voltage network and the IEEE 30-bus network show that the minimum number of measurements for an observable system is not influenced by the degree of meshing. However, a higher degree of meshing has a positive effect on the reliability of the monitoring system as the number of critical measurements and sets is reduced. |
Zusätzliche Informationen: | CIRED 2024 Vienna Workshop, Vienna, Austria, 19.06.2024 - 20.06.2024 |
Fachbereich(e)/-gebiet(e): | 18 Fachbereich Elektrotechnik und Informationstechnik 18 Fachbereich Elektrotechnik und Informationstechnik > Institut für Elektrische Energiesysteme > Elektrische Energieversorgung unter Einsatz Erneuerbarer Energien 18 Fachbereich Elektrotechnik und Informationstechnik > Institut für Elektrische Energiesysteme |
Hinterlegungsdatum: | 13 Nov 2024 13:26 |
Letzte Änderung: | 13 Nov 2024 13:26 |
PPN: | |
Export: | |
Suche nach Titel in: | TUfind oder in Google |
Frage zum Eintrag |
Optionen (nur für Redakteure)
Redaktionelle Details anzeigen |