Balzer, Gerd ; Saçiak, Andreas ; Hanson, Jutta (2024)
Calculation of short-circuit currents of HVDC installations for the planning and operation of secure AC networks.
27th Speedam Meeting. Ischia, Italy (19.06.2024 - 21.06.2024)
Konferenzveröffentlichung, Bibliographie
Kurzbeschreibung (Abstract)
In principle, HVDC installations contribute to a short circuit in the AC network, so this short-circuit current must be taken into account when designing the installations. Because of the increased use of converter installations in three- phase networks (AC), it is necessary to consider their contribution to a short circuit in the network calculation. While self-commutated installations (VSC) are already taken into account by a suitable current source in the currently valid IEC Standard "Short-Circuit Calculation", this standard misses the instruction how to proceed in case of a line- commutated installation (LCC). For this reason, this report presents a procedure to calculate the discharge process of the DC side of a line-commutated system as a voltage source. The results are compared with detailed simulations taking into account the control and commutation errors during a short circuit. This procedure can be adopted in a revision of the relevant IEC Standard.
Typ des Eintrags: | Konferenzveröffentlichung |
---|---|
Erschienen: | 2024 |
Autor(en): | Balzer, Gerd ; Saçiak, Andreas ; Hanson, Jutta |
Art des Eintrags: | Bibliographie |
Titel: | Calculation of short-circuit currents of HVDC installations for the planning and operation of secure AC networks |
Sprache: | Englisch |
Publikationsjahr: | 19 Juni 2024 |
Veranstaltungstitel: | 27th Speedam Meeting |
Veranstaltungsort: | Ischia, Italy |
Veranstaltungsdatum: | 19.06.2024 - 21.06.2024 |
Kurzbeschreibung (Abstract): | In principle, HVDC installations contribute to a short circuit in the AC network, so this short-circuit current must be taken into account when designing the installations. Because of the increased use of converter installations in three- phase networks (AC), it is necessary to consider their contribution to a short circuit in the network calculation. While self-commutated installations (VSC) are already taken into account by a suitable current source in the currently valid IEC Standard "Short-Circuit Calculation", this standard misses the instruction how to proceed in case of a line- commutated installation (LCC). For this reason, this report presents a procedure to calculate the discharge process of the DC side of a line-commutated system as a voltage source. The results are compared with detailed simulations taking into account the control and commutation errors during a short circuit. This procedure can be adopted in a revision of the relevant IEC Standard. |
Fachbereich(e)/-gebiet(e): | 18 Fachbereich Elektrotechnik und Informationstechnik 18 Fachbereich Elektrotechnik und Informationstechnik > Institut für Elektrische Energiesysteme > Elektrische Energieversorgung unter Einsatz Erneuerbarer Energien 18 Fachbereich Elektrotechnik und Informationstechnik > Institut für Elektrische Energiesysteme |
Hinterlegungsdatum: | 22 Aug 2024 08:54 |
Letzte Änderung: | 22 Aug 2024 08:54 |
PPN: | |
Export: | |
Suche nach Titel in: | TUfind oder in Google |
Frage zum Eintrag |
Optionen (nur für Redakteure)
Redaktionelle Details anzeigen |