Kurzbeschreibung (Abstract)

In principle, HVDC installations contribute to a short circuit in the AC network, so this short-circuit current must be taken into account when designing the installations. Because of the increased use of converter installations in three- phase networks (AC), it is necessary to consider their contribution to a short circuit in the network calculation. While self-commutated installations (VSC) are already taken into account by a suitable current source in the currently valid IEC Standard "Short-Circuit Calculation", this standard misses the instruction how to proceed in case of a line- commutated installation (LCC). For this reason, this report presents a procedure to calculate the discharge process of the DC side of a line-commutated system as a voltage source. The results are compared with detailed simulations taking into account the control and commutation errors during a short circuit. This procedure can be adopted in a revision of the relevant IEC Standard.

Typ des Eintrags: Konferenzveröffentlichung
Erschienen: 2024
Autor(en): Balzer, Gerd ; Saçiak, Andreas ; Hanson, Jutta
Art des Eintrags: Bibliographie
Titel: Calculation of short-circuit currents of HVDC installations for the planning and operation of secure AC networks
Sprache: Englisch
Publikationsjahr: 19 Juni 2024
Veranstaltungstitel: 27th Speedam Meeting
Veranstaltungsort: Ischia, Italy
Veranstaltungsdatum: 19.06.2024 - 21.06.2024
Kurzbeschreibung (Abstract):

In principle, HVDC installations contribute to a short circuit in the AC network, so this short-circuit current must be taken into account when designing the installations. Because of the increased use of converter installations in three- phase networks (AC), it is necessary to consider their contribution to a short circuit in the network calculation. While self-commutated installations (VSC) are already taken into account by a suitable current source in the currently valid IEC Standard "Short-Circuit Calculation", this standard misses the instruction how to proceed in case of a line- commutated installation (LCC). For this reason, this report presents a procedure to calculate the discharge process of the DC side of a line-commutated system as a voltage source. The results are compared with detailed simulations taking into account the control and commutation errors during a short circuit. This procedure can be adopted in a revision of the relevant IEC Standard.

Fachbereich(e)/-gebiet(e): 18 Fachbereich Elektrotechnik und Informationstechnik
18 Fachbereich Elektrotechnik und Informationstechnik > Institut für Elektrische Energiesysteme > Elektrische Energieversorgung unter Einsatz Erneuerbarer Energien
18 Fachbereich Elektrotechnik und Informationstechnik > Institut für Elektrische Energiesysteme
Hinterlegungsdatum: 22 Aug 2024 08:54
Letzte Änderung: 22 Aug 2024 08:54
PPN:
Export:
Suche nach Titel in: TUfind oder in Google
Frage zum Eintrag Frage zum Eintrag

Optionen (nur für Redakteure)
Redaktionelle Details anzeigen Redaktionelle Details anzeigen