TU Darmstadt / ULB / TUbiblio

Requirements for onsite test systems for the after-installation test of HVDC cable systems

Marcel, Stöckli ; Gamlin, Michael ; Stuckenholz, Carl-Hendrik ; Müller, Tobias ; Eckert, Manuel
Hrsg.: Conseil International des Grands Réseaux Électriques (CIGRE) (2024)
Requirements for onsite test systems for the after-installation test of HVDC cable systems.
50th CIGRE Paris Session 2024. Paris, France (25.08.2024 - 30.08.2024)
Konferenzveröffentlichung, Bibliographie

Kurzbeschreibung (Abstract)

Any HVDC cable system must undergo an overvoltage test after installation and prior to operation. According to TB 841 [1], the suggested test voltage is 1.45x U0 for 60 min for extruded (XLPE) HVDC cable systems and 1.4x U0 for 60 min for mass impregnated (MI) HVDC cable systems. An onsite HVDC test system, designed for these tests, consists of a DC source to charge up the cable system, an external voltage divider to measure the applied DC voltage, a protection resistor to protect the DC source in case of a cable system breakdown and a discharge resistor to discharge the cable system in short time after the HVDC test (Fig. 1). In the future, after repair tests are also expected. The paper presents the requirements for the onsite HVDC test system and its components.

Typ des Eintrags: Konferenzveröffentlichung
Erschienen: 2024
Autor(en): Marcel, Stöckli ; Gamlin, Michael ; Stuckenholz, Carl-Hendrik ; Müller, Tobias ; Eckert, Manuel
Art des Eintrags: Bibliographie
Titel: Requirements for onsite test systems for the after-installation test of HVDC cable systems
Sprache: Englisch
Publikationsjahr: August 2024
Veranstaltungstitel: 50th CIGRE Paris Session 2024
Veranstaltungsort: Paris, France
Veranstaltungsdatum: 25.08.2024 - 30.08.2024
Kurzbeschreibung (Abstract):

Any HVDC cable system must undergo an overvoltage test after installation and prior to operation. According to TB 841 [1], the suggested test voltage is 1.45x U0 for 60 min for extruded (XLPE) HVDC cable systems and 1.4x U0 for 60 min for mass impregnated (MI) HVDC cable systems. An onsite HVDC test system, designed for these tests, consists of a DC source to charge up the cable system, an external voltage divider to measure the applied DC voltage, a protection resistor to protect the DC source in case of a cable system breakdown and a discharge resistor to discharge the cable system in short time after the HVDC test (Fig. 1). In the future, after repair tests are also expected. The paper presents the requirements for the onsite HVDC test system and its components.

ID-Nummer: Artikel-ID: 11755
Fachbereich(e)/-gebiet(e): 18 Fachbereich Elektrotechnik und Informationstechnik
18 Fachbereich Elektrotechnik und Informationstechnik > Institut für Elektrische Energiesysteme > Hochspannungstechnik
18 Fachbereich Elektrotechnik und Informationstechnik > Institut für Elektrische Energiesysteme
Hinterlegungsdatum: 09 Jul 2024 08:09
Letzte Änderung: 09 Jul 2024 08:09
PPN:
Export:
Suche nach Titel in: TUfind oder in Google
Frage zum Eintrag Frage zum Eintrag

Optionen (nur für Redakteure)
Redaktionelle Details anzeigen Redaktionelle Details anzeigen