Pfendler, A. ; Riess, P. ; Choudhury, S. ; Steppan, R. ; Hebing, A. ; Hanson, J. (2023)
Comparison of RMS and EMT models of an inverter-based generator with fast-frequency response.
27th International Conference on Electricity Distribution (CIRED 2023). Rome, Italy (12.06.2023-15.06.2023)
doi: 10.1049/icp.2023.0620
Konferenzveröffentlichung, Bibliographie
Kurzbeschreibung (Abstract)
This paper investigates the dynamic frequency support of an inverter-based generator with fast frequency response in the medium-voltage grid and compares the results in RMS and EMT simulations. For synchronous generator dominated power systems, RMS-type models are widely used due to the relatively slow dynamics. In contrast, power electronics act on a faster time scale and EMT-type simulations are necessary to model and investigate the behaviour in detail. For bulk system modelling, inverter- based generators are usually considered as simplified models. This paper compares the RMS and EMT model of an inverter-based generator in a simple medium-voltage testbench and shows that the average value model leads to differences in RMS and EMT simulations when evaluating the dynamic frequency in time domain. The reason is that the local frequency measurement for the inverter control is delayed in RMS during transient processes.
Typ des Eintrags: | Konferenzveröffentlichung |
---|---|
Erschienen: | 2023 |
Autor(en): | Pfendler, A. ; Riess, P. ; Choudhury, S. ; Steppan, R. ; Hebing, A. ; Hanson, J. |
Art des Eintrags: | Bibliographie |
Titel: | Comparison of RMS and EMT models of an inverter-based generator with fast-frequency response |
Sprache: | Englisch |
Publikationsjahr: | 29 September 2023 |
Verlag: | IET |
Veranstaltungstitel: | 27th International Conference on Electricity Distribution (CIRED 2023) |
Veranstaltungsort: | Rome, Italy |
Veranstaltungsdatum: | 12.06.2023-15.06.2023 |
DOI: | 10.1049/icp.2023.0620 |
URL / URN: | https://ieeexplore.ieee.org/document/10267144 |
Zugehörige Links: | |
Kurzbeschreibung (Abstract): | This paper investigates the dynamic frequency support of an inverter-based generator with fast frequency response in the medium-voltage grid and compares the results in RMS and EMT simulations. For synchronous generator dominated power systems, RMS-type models are widely used due to the relatively slow dynamics. In contrast, power electronics act on a faster time scale and EMT-type simulations are necessary to model and investigate the behaviour in detail. For bulk system modelling, inverter- based generators are usually considered as simplified models. This paper compares the RMS and EMT model of an inverter-based generator in a simple medium-voltage testbench and shows that the average value model leads to differences in RMS and EMT simulations when evaluating the dynamic frequency in time domain. The reason is that the local frequency measurement for the inverter control is delayed in RMS during transient processes. |
Zusätzliche Informationen: | Art.No.: 10453 |
Fachbereich(e)/-gebiet(e): | 18 Fachbereich Elektrotechnik und Informationstechnik 18 Fachbereich Elektrotechnik und Informationstechnik > Institut für Elektrische Energiesysteme > Elektrische Energieversorgung unter Einsatz Erneuerbarer Energien 18 Fachbereich Elektrotechnik und Informationstechnik > Institut für Elektrische Energiesysteme |
Hinterlegungsdatum: | 19 Okt 2023 10:18 |
Letzte Änderung: | 19 Okt 2023 10:18 |
PPN: | |
Export: | |
Suche nach Titel in: | TUfind oder in Google |
Frage zum Eintrag |
Optionen (nur für Redakteure)
Redaktionelle Details anzeigen |