Method for determining background distortion of a real MV-network based on measured data

Schweinsberg, Carl ; Hanson, Jutta (2022)
Method for determining background distortion of a real MV-network based on measured data.
IEEE International Conference on Power System Technology. Kuala Lumpur, Malaysia (12.09.2022-14.09.2022)
doi: 10.1109/POWERCON53406.2022.9929898
Konferenzveröffentlichung, Bibliographie

Kurzbeschreibung (Abstract)

As part of the project EnEff: Stadt Campus Lichtwiese, a permanent Power Quality-Monitoring System has been installed in the medium-voltage network of the Campus Lichtwiese of Technical University of Darmstadt. The system enables measurement of harmonic distortion at each busbar of the network. The data measured is used to parametrise the network model of the campus for analysing its harmonic behaviour. In the course of this paper, the Campus Lichtwiese as well as the implemented monitoring system are presented. The latter is evaluated with regard to its measurement uncertainty. A method is introduced which, based on the measurement data and the network model of the campus, determines the background distortion at the point of common coupling (PCC) of the campus network, which in turn is used to parametrise the network model. Therefore the background distortion is firstly determined and secondly integrated into the model. The comparison between measurement and simulation at the PCC shows good conformity.

Typ des Eintrags: Konferenzveröffentlichung
Erschienen: 2022
Autor(en): Schweinsberg, Carl ; Hanson, Jutta
Art des Eintrags: Bibliographie
Titel: Method for determining background distortion of a real MV-network based on measured data
Sprache: Englisch
Publikationsjahr: 4 November 2022
Verlag: IEEE
Buchtitel: 2022 IEEE International Conference on Power Systems Technology (POWERCON)
Veranstaltungstitel: IEEE International Conference on Power System Technology
Veranstaltungsort: Kuala Lumpur, Malaysia
Veranstaltungsdatum: 12.09.2022-14.09.2022
DOI: 10.1109/POWERCON53406.2022.9929898
URL / URN: https://ieeexplore.ieee.org/document/9929898
Zugehörige Links:
Kurzbeschreibung (Abstract):

As part of the project EnEff: Stadt Campus Lichtwiese, a permanent Power Quality-Monitoring System has been installed in the medium-voltage network of the Campus Lichtwiese of Technical University of Darmstadt. The system enables measurement of harmonic distortion at each busbar of the network. The data measured is used to parametrise the network model of the campus for analysing its harmonic behaviour. In the course of this paper, the Campus Lichtwiese as well as the implemented monitoring system are presented. The latter is evaluated with regard to its measurement uncertainty. A method is introduced which, based on the measurement data and the network model of the campus, determines the background distortion at the point of common coupling (PCC) of the campus network, which in turn is used to parametrise the network model. Therefore the background distortion is firstly determined and secondly integrated into the model. The comparison between measurement and simulation at the PCC shows good conformity.

Fachbereich(e)/-gebiet(e): 18 Fachbereich Elektrotechnik und Informationstechnik
18 Fachbereich Elektrotechnik und Informationstechnik > Institut für Elektrische Energiesysteme > Elektrische Energieversorgung unter Einsatz Erneuerbarer Energien
18 Fachbereich Elektrotechnik und Informationstechnik > Institut für Elektrische Energiesysteme
Hinterlegungsdatum: 12 Dez 2022 08:12
Letzte Änderung: 02 Feb 2023 11:36
PPN: 504269933
Export:
Suche nach Titel in: TUfind oder in Google
Frage zum Eintrag Frage zum Eintrag

Optionen (nur für Redakteure)
Redaktionelle Details anzeigen Redaktionelle Details anzeigen