TU Darmstadt / ULB / TUbiblio

Experience Report of Potential Free Temperature Measurement with commercially available Pyrometers in gas insulated systems

Hallas, Martin ; Moxter, Julian ; Hinrichsen, Volker ; Juhre, Karsten ; Tenzer, Michael (2023)
Experience Report of Potential Free Temperature Measurement with commercially available Pyrometers in gas insulated systems.
VDE Hochspannungstechnik 2022. Berlin, Germany (08.-10.11.2022)
doi: 10.26083/tuprints-00023106
Konferenzveröffentlichung, Zweitveröffentlichung, Verlagsversion

Kurzbeschreibung (Abstract)

A potential free temperature measurement in gas insulated switchgear and lines (GIS/GIL) was investigated within an HVDC research project, because the temperature is of high importance during development and operation of HVDC equipment. Infrared spectrum measurement of the heated inner conductor by pyrometer sensors has emerged as the best technical solution for HVDC GIS/GIL. To optimize the infrared emission of the inner conductor, it was painted with black varnish. The sensor had to be adjusted to the infrared transmission of the pressurized insulating gas atmosphere. Experiences as well as methods to perform such a calibration are shown in the paper. A calibration by adjusting transmission and emission coefficients inside the sensor software did not succeeded, because the coefficients differed for variable sensor ambient temperatures. A successful calibration was possible by considering two major variables: the pyrometer output as well as the sensor ambient temperature. However, certain limits of the pyrometer measurement in GIS/GIL were observed as well. The EMC performance of the pyrometer was improved by an additional electronic unit, which protects the commercial electronics. Overall, the potential free temperature measurement could be performed during the long-term operation of the regarded HVDC GIL system. Typical temperature curves based on the calibrated pyrometer sensor are shown.

Typ des Eintrags: Konferenzveröffentlichung
Erschienen: 2023
Autor(en): Hallas, Martin ; Moxter, Julian ; Hinrichsen, Volker ; Juhre, Karsten ; Tenzer, Michael
Art des Eintrags: Zweitveröffentlichung
Titel: Experience Report of Potential Free Temperature Measurement with commercially available Pyrometers in gas insulated systems
Sprache: Englisch
Publikationsjahr: 2023
Ort: Darmstadt
Publikationsdatum der Erstveröffentlichung: 2022
Verlag: VDE Verlag
Buchtitel: VDE Hochspannungstechnik : 8. – 10. November 2022 in Berlin
Reihe: ETG-Fachberichte
Band einer Reihe: 169
Kollation: 7 ungezählte Seiten
Veranstaltungstitel: VDE Hochspannungstechnik 2022
Veranstaltungsort: Berlin, Germany
Veranstaltungsdatum: 08.-10.11.2022
DOI: 10.26083/tuprints-00023106
URL / URN: https://tuprints.ulb.tu-darmstadt.de/23106
Zugehörige Links:
Herkunft: Zweitveröffentlichungsservice
Kurzbeschreibung (Abstract):

A potential free temperature measurement in gas insulated switchgear and lines (GIS/GIL) was investigated within an HVDC research project, because the temperature is of high importance during development and operation of HVDC equipment. Infrared spectrum measurement of the heated inner conductor by pyrometer sensors has emerged as the best technical solution for HVDC GIS/GIL. To optimize the infrared emission of the inner conductor, it was painted with black varnish. The sensor had to be adjusted to the infrared transmission of the pressurized insulating gas atmosphere. Experiences as well as methods to perform such a calibration are shown in the paper. A calibration by adjusting transmission and emission coefficients inside the sensor software did not succeeded, because the coefficients differed for variable sensor ambient temperatures. A successful calibration was possible by considering two major variables: the pyrometer output as well as the sensor ambient temperature. However, certain limits of the pyrometer measurement in GIS/GIL were observed as well. The EMC performance of the pyrometer was improved by an additional electronic unit, which protects the commercial electronics. Overall, the potential free temperature measurement could be performed during the long-term operation of the regarded HVDC GIL system. Typical temperature curves based on the calibrated pyrometer sensor are shown.

Freie Schlagworte: potential free temperature measurement, pyrometer, gas-insulated system
Status: Verlagsversion
URN: urn:nbn:de:tuda-tuprints-231062
Sachgruppe der Dewey Dezimalklassifikatin (DDC): 600 Technik, Medizin, angewandte Wissenschaften > 620 Ingenieurwissenschaften und Maschinenbau
Fachbereich(e)/-gebiet(e): 18 Fachbereich Elektrotechnik und Informationstechnik
18 Fachbereich Elektrotechnik und Informationstechnik > Institut für Elektrische Energiesysteme > Hochspannungstechnik
18 Fachbereich Elektrotechnik und Informationstechnik > Institut für Elektrische Energiesysteme